Rooftop access requirements for buildings with solar panel installations

Summary#

Introduction 0640-2026, sponsored by Council Member Lincoln Restler, would amend the New York City Fire Code. Its stated goal is to change rooftop access rules for buildings with solar panels; the bill is not yet law and is waiting in committee after referral on February 12, 2026.

  • It would reduce the required width of the general rooftop clear paths from 6 feet to 4 feet. The paths must still be 9 feet high and meet other access and safety requirements.
  • For certain flat-roofed buildings 25 feet or less wide or deep, permanent rooftop features could reduce a clear path to 3 feet in places, rather than the current text’s 4-foot minimum. The maximum encroachment would increase from 2 feet to 3 feet.
  • It would allow solar panels to obstruct a clear path if a one-person, tool-free, approved device can move the panels out of the path.
  • It would let qualifying adjoining rooftops be treated together for some access and obstruction rules when solar panels are installed. The buildings must be R-2 or R-3, the roofs must be at the same height and touch, have no bulkheads, and each be no more than 25 feet wide.
  • For consolidated roofs, owners would have to provide specified clear paths, submit an authorized plan to the Department of Buildings, notify the department, post signs showing inverter shutoff locations, and restore or alter roofs if required access is no longer available.

What it means for you#

  • Building owners installing solar panels: The bill would allow some panels to obstruct rooftop paths if they can be moved safely by one person without a tool using an approved device. Owners using the adjoining-rooftop option would have to meet its access, application, notification and signage requirements.
  • Owners of qualifying adjoining buildings: They would have to authorize the application plan together. The combined-roof option would require a 6-foot-wide path along the front of the roofs and a 4-foot-wide path along the rear, each 9 feet high. Access to the rear would also need a 6-foot-wide path on at least every other building.
  • Firefighters and building occupants: Paths would be narrower under the general rule. The bill would still require access to rooftop features such as fire escapes, skylights and hatches, and would prohibit paths that require firefighters to walk on flush-mounted solar panels or other energized equipment.
  • Other residents and businesses: The bill does not directly change taxes, benefits or general rooftop access rights.

Money#

No cost information is available in the supplied material.

  • The bill would require certain building owners to meet access, application, notification and signage rules, but gives no estimate of their costs.
  • It does not specify public spending or staffing.

What is unclear#

  • The Fire Code text in force was not supplied, so the current-law comparison is based on the bill’s bracketed edits and not independently verified against the full current code.
  • The bill does not explain how the Department of Buildings or the department receiving installation notifications would review or enforce these requirements, or set timelines or appeal rules.
  • It does not define “substantially all” of a rooftop or explain how to resolve disagreements about whether a solar design requires that much coverage.
  • The bill does not say how quickly owners must restore or alter a roof if access between adjoining rooftops is lost.

Case for#

  • A possible argument for the bill is that it would make room for solar panels on some narrow roofs while keeping specified paths for firefighters.
  • The movable-panel option could allow panels to cover a path when needed, while requiring a way to clear it without tools.
  • The adjoining-rooftop option could allow solar installations to use a shared access arrangement, but only for buildings meeting listed conditions and with owner authorization.

Case against#

  • One concern is that reducing the general path from 6 feet to 4 feet—and allowing some paths to narrow to 3 feet—could leave less space for rooftop access.
  • The shared-roof option depends on continued access across adjoining buildings. If that access ends, the bill requires restoration or alteration but does not set a deadline or explain how compliance would be checked.
  • The bill does not specify how the approved movable-panel devices would be tested or how owners would show they remain usable.